Row-level CDU

High-capacity coolant distribution for multi-rack AI and HPC deployments. Two product series from 300 kW to 1,700 kW, with redundant pumps, intelligent controls, and CE & UL certified models for global projects.

300 – 1,700 kW Redundant Pumps Step-less Flow Control CE & UL Certified

Built for High-Density Cooling

Wide Capacity Range

Two product series covering 300 kW to 1,700 kW. Match cooling capacity to any rack density — from standard enterprise workloads to GPU-intensive AI training clusters.

Redundant Architecture

Key components including pumps and valves are fully redundant. Dual power input and automatic switchover keep the system running without shutdown during maintenance or power events.

Intelligent Flow Control

Multi-mode pressure differential control with step-less flow adjustment. Supports cold standby, hot standby, independent operation, and group control across multiple CDUs.

Global Certification

CFUS series (600–1,700 kW) complies with both CE and UL standards, enabling deployment in North America, Europe, and regulated international markets.

Modular & Serviceable

Modular cabinet design with front and rear access for maintenance. Supports automatic online coolant refilling and configurable pipe direction, filter class, and communication options.

Open Protocol Integration

RS485 and RJ45 interfaces with Modbus, TCP, and UDP protocol support. Compatible with BMS, DCIM, and third-party monitoring platforms for centralized facility management.

Technical Specifications

CF-GCDU Series — 300–410 kW
ParameterCF-GCDU-300CF-GCDU-340CF-GCDU-370CF-GCDU-410
Rated Heat Transfer Capacity300 kW340 kW370 kW410 kW
Net Weight670 kg720 kg670 kg720 kg
Dimensions (H × W × D)2.2 × 0.6 × 1.2 m2.2 × 0.6 × 1.2 m2.2 × 0.6 × 1.2 m2.2 × 0.6 × 1.2 m
Power SupplyAC380AC380AC380AC380
Secondary Loop
CoolantDI waterDI waterDI waterDI water
Supply / Return Temp.40 / 50 °C40 / 50 °C40 / 50 °C40 / 50 °C
Pipe ConnectionDN65DN65DN65DN65
Rated Flow Rate436 L/min494 L/min537 L/min595 L/min
Max. Pressure10 bar10 bar10 bar10 bar
Primary Loop
CoolantDI waterDI waterDI waterDI water
Supply / Return Temp.35 / 45 °C35 / 45 °C35 / 45 °C35 / 45 °C
Pipe ConnectionDN65DN65DN65DN65
Coolant Supply Temp. Range8 – 35 °C8 – 35 °C8 – 35 °C8 – 35 °C
Max. Pressure10 bar10 bar10 bar10 bar
CFUS-GCDU Series — 600–1,700 kW  |  CE & UL Certified
ParameterCFUS-GCDU-600CFUS-GCDU-1000CFUS-GCDU-1250CFUS-GCDU-1700
Rated Heat Transfer Capacity600 kW1,000 kW1,250 kW1,700 kW
Net Weight725 kg805 kg1,000 kg1,130 kg
Dimensions (H × W × D)2.2 × 0.6 × 1.2 m2.2 × 0.6 × 1.2 m2.05 × 0.9 × 1.2 m2.05 × 0.9 × 1.2 m
Power SupplyAC480 / AC380AC480 / AC380AC480 / AC380AC480 / AC380
Secondary Loop
CoolantDI waterDI waterDI waterDI water
Supply / Return Temp.35 / 50 °C35 / 50 °C35 / 50 °C35 / 50 °C
Pipe ConnectionDN80DN80DN100DN100
Rated Flow Rate580 L/min967 L/min1,209 L/min1,644 L/min
Max. Pressure10 bar10 bar10 bar10 bar
Primary Loop
CoolantDI waterDI waterDI waterDI water
Supply / Return Temp.31 / 42 °C31 / 42 °C31 / 42 °C31 / 42 °C
Pipe ConnectionDN80DN80DN100DN100
Coolant Supply Temp. Range8 – 35 °C8 – 35 °C8 – 35 °C8 – 35 °C
Max. Pressure10 bar10 bar10 bar10 bar
Specifications may vary based on site conditions. Temperature, pressure drop, and flow rate of the secondary loop can be adjusted automatically according to actual load. Contact our engineers for project-specific calculations.