DSI — Indoor Free Cooling Unit

Indoor dual-cooling-source heat rejection module combining natural free cooling and mechanical cooling in a single unit. Maximizes free cooling hours to reduce chiller dependency and energy consumption.

Up to 650 kW Free Cooling + Mechanical Cooling Dynamic Air-to-Liquid Ratio 10+ Year Service Life

Year-Round Free Cooling, Indoors

Dual-Source Cooling

Combines natural free cooling and mechanical cooling in one integrated unit. In favorable ambient conditions, chillers can be shut down entirely — achieving ultra-low energy consumption.

Water-Free Heat Rejection

Uses air as the cooling medium instead of water, eliminating cooling tower water consumption and the associated chemical treatment requirements.

Intelligent Multi-Mode Control

Supports cold standby, hot standby, single-machine, group control, and local/remote operation. Multiple units automatically form a network for coordinated management.

Dynamic Air-to-Liquid Ratio

Wide range of cooling capacity and temperature regulation. The air-to-liquid ratio adjusts dynamically based on ambient conditions to maintain optimal efficiency.

24/7 Reliability

Designed for continuous operation — 24 hours a day, 365 days a year — with a service life of no less than 10 years.

Open Protocol Integration

RS485 and RJ45 interfaces with Modbus RTU and Modbus TCP support. Compatible with BMS and third-party monitoring platforms.

Technical Specifications

DSI (Indoor Dual-Cooling-Source) — CF-DSI-1000
ParameterNatural CoolingMechanical Cooling
Rated Heat Exchange Capacity350 kW (liquid cooling)650 kW (air cooling)
Dimensions (L × W × H)1,800 × 850 × 2,000 mm1,800 × 850 × 2,000 mm
Net Weight2,000 kg2,000 kg
Cooling MediumWaterWater
Rated Flow Rate60 m³/h33 m³/h
Flow Resistance≤ 100 kPa
Ambient Temperature40 °C18 °C
Supply Liquid Temperature50 °C26 °C
Return Liquid Temperature50 °C26 °C
Pipe Interface Size101.6 mm chuck76.1 mm chuck
Max. Power Consumption≤ 100 kW≤ 100 kW
Power SpecificationAC380V / 3 / 50HzAC380V / 3 / 50Hz
Cooling FormAir cooling + mechanical coolingAir cooling + mechanical cooling
CommunicationRS485, RJ45RS485, RJ45
ProtocolModbus RTU, Modbus TCPModbus RTU, Modbus TCP
Noise Level75 dB(A) @ 15 m75 dB(A) @ 15 m
The air-to-liquid ratio can be automatically adjusted based on actual site conditions. Technical parameters can be selected and customized according to application requirements. Contact our engineers for project-specific consultation.