Indoor dual-cooling-source heat rejection module combining natural free cooling and mechanical cooling in a single unit. Maximizes free cooling hours to reduce chiller dependency and energy consumption.

Combines an EC fan dry cooler for natural free cooling with a mechanical cooling module. In favorable ambient conditions, chillers can be shut down entirely for ultra-low energy operation.
Uses air as the primary cooling medium, eliminating cooling tower water consumption and the associated chemical treatment and maintenance overhead.
Supports cold standby, hot standby, single-machine, group control, and local/remote operation. Multiple units automatically form a network for coordinated management.
Wide range of cooling capacity and temperature regulation. The air-to-liquid ratio adjusts dynamically based on ambient conditions to maintain optimal efficiency across seasons.
Designed for continuous outdoor operation — 24 hours a day, 365 days a year — with a service life of no less than 10 years.
RS485 and RJ45 interfaces with Modbus RTU protocol support. Compatible with BMS and third-party monitoring platforms for centralized facility management.
| Parameter | Dry Cooler | Mechanical Cooling |
|---|---|---|
| Rated Heat Transfer Capacity | 700 kW (liquid cooling) | 300 kW (air cooling) |
| Dimensions (L × W × H) | 8,000 × 3,000 × 3,000 mm | 2,000 × ≤ 3,000 × ≤ 3,000 mm |
| Net Weight | 3,000 kg | 1,000 kg |
| Cooling Medium | Water | Water |
| Rated Flow Rate | 60 m³/h | 30 m³/h |
| Flow Resistance | ≤ 100 kPa | — |
| Ambient Temperature | 35 °C | 35 °C |
| Supply Liquid Temperature | 40 °C | 18 °C |
| Return Liquid Temperature | 50 °C | 26 °C |
| External Pipe Interface | DN100 flange | 76.1 mm chuck |
| Max. Power Consumption | 38.4 kW | 90 kW |
| Power Specification | AC380V / 3 / 50Hz | AC380V / 3 / 50Hz |
| Cooling Form | Air cooling (EC fans) | Water cooling |
| Communication | RS485, RJ45 | RS485, RJ45 |
| Protocol | Modbus RTU | Modbus RTU |
| Noise Level | 75 dB(A) @ 15 m | 75 dB(A) @ 15 m |